Wilo
Centrifugal
Stratos MAXO-D
Technical Specifications
Pressure
≤ 16 bar
Liquid temperature
-10 … +110 °C
Viscosity
≤ 1 cSt
DNoutlet
32 ≤ DNoutlet ≤ 80
Drive type
electric
Installation
horizontal,vertical
Seal type
Wet rotor (glandless)
Price
On request
Wilo Stratos MAXO-D: Smart glandless twin-head circulator with screwed connection or flange connection, EC motor with integrated electronic power adjustment.
Key technical parameters
- Permissible temperature range -10 °C to +110 °C, -10 °C to +90 °C
- Mains connection 1~230 V, 50/60 Hz
- IP rating IPX4D
- Screwed connection DN 30 (RP 1 1/4)
- Flange connection DN 32 to DN 80
- Max. operating pressure of standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)
- Insulation class: F
- Interference emission in acc. with: EN 61800-3:2004+A1:2012/residential environment (C1)
- Interference immunity in acc. with: EN 61800-3:2004+A1:2012 / industrial environment (C2)
- Drive: Electric motor
Media handled
- Liquids: Water (clean), Glycol
- Media properties: Low viscosity
Applications and industries
- Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems.
- Field of application The pump facilitates an operation via precise setting of the control mode for the system-specific application (e.g. for radiator, underfloor heating, ceiling cooling).
- Heating Radiator
HVAC
No reviews yet for this pump series.